2014-07-18 10:41:071) 107.7 E ADDRESS PLANTER AND DECK DRAINS. A DEMO PLAN
 WAS NOT INCLUDED. DO DRAINS EXIST? PROVIDE A PLAN VIEW
 AND ISO. SHOW DRAIN SIZING WITH PROJECTED AREA FOR EACH
 DRAIN. SHOW PIPING TO POINT OF DISPOSAL.
  
 2) 107.7 C SHEET M-2 GAS PLAN IS INCOMPLETE. PROVIDE
 LONGEST LENGTH, PIPE SECTION LENGTHS, PIPE SIZING 2010
 FBC FUEL GAS TABLE(S) USED TO SIZE PIPING PER LOAD,
 MATERIAL, AND GAS PRESSURE. SHOW LOCATION OF NEW BBQ
 GRILLS.
  
 JOE CROASDALE
 PLUMBING PLANS EXAMINER
 TEL. (954) 828-5296
 FAX (954) 828-5275
 JCROASDALE@FORTLAUDERDALE.GOV
2014-07-11 08:53:171- MISSING A RESPONSE SHEET FOR PREVIOUS COMMENTS.
 2- FLAT AND ISO DO NOT MATCH.
 3- THE SANITARY LINES ON FLAT ARE TOO LIGHT, PLEASE
 MAKE BOLDER FOR BETTER VISIBILITY.
 4- FLAT DRY VENTS SHOWN SEE FPC 905 VENT CONNECTIONS
 AND GRADES
 5- SHOW DRAINAGE PATTERN FITTINGS ON ALL FITTINGS
 INDICATING DIRECTION OF FLOW, A NOTE IS NOT
 SUFFICIENT.
 6- USE CORRECT NAME FOR TYPE OF FIXTURES, PLAN IS
 SHOWING SINKS IN THE BATHROOMS, SHOULD BE LAVS, SINKS
 CANNOT BE PART OF BATHROOM GROUPS.
 7- PREVIOUS COMMENTS ADDRESSED THE GAS PIPING, WAS GAS
 DELETED, PLEASE CARIFY.
 8- PROVIDE INFO AND SPECS FOR POOL EQUIPMENT AND
 COLLECTOR TANK
 GREG DIAZ
 PLUMBING PLAN REVIEW
2014-05-30 15:54:401) 107.7 C GAS. INCLUDE LONGEST LENGTH, PIPE SECTION
 LENGTHS, PIPE SIZING, 2010 FBC FUEL GAS TABLE(S) TO
 SIZE PIPING,AND SHOW MWTER ON PLAN VIEW.
  
 2) 706.3 SHOW SANITARY FITTINGS INSTALLED IN DIRECTION
 OF FLOW.
  
 3) 107.7.1 PROVIDE FOR HANDICAP REQUIREMENTS. HEIGHTS,
 CLEARANCES, CLEAR FLOOR SPACE, SHOWER DIMENTIONS AND
 CONTROLS, HI-LOW DRINKING FOUNTAIN, GRAB BARS, ETC.
  
 4) 107.7 E 4 PROVIDE SANITARY PLAN VIEW FOR REQUIRED
 HI-LOW DRINKING FOUNTAIN. RELIEF VENT MAY BE REQUIRED.
  
 5) 917.4 DRINKING FOUNTAIN AAV SHALL BE LOCATED A
 MINIMUM OF 4" ABOVE THE FIXTURE DRAIN BEING VENTED.
  
 6) 107.7.1 URINALS AND TOILETS ARE FLUSHOMETER
 TYPE.RISER SHOWS 1/2" SUPPLIES. PROVIDE SPEC'S/CUTS FOR
 FIXTURES.
  
 7) 604.4 MAXIMUM FLOW RATES AND CONSUMPTION FOR
 FIXTURES, FITTINGS, AND APPLIANCES SHALL BE PER TABLE
 604.4 EFFECTIVE 2-1-14 WHICH I HAVE ATTACHED TO SHEET
 P-2 JOB COPY.
  
 8) 902.1 TRAP SEAL PROTECTION AND 901.2.1 VENTING
 REQUIRED. EVERY TRAP AND TRAPPED FIXTURE SHALL BE
 VENTED IN ACCORDANCE WITH ONE OF THE VENTING METHODS
 SPECIFIED IN CHAPTER 9.
  
 9) 424.1.9.5 A HOSE BIBB WITH A VACUUM BREAKER SHALL BE
 LOCATED IN THE EQUIPMENT ROOM.
  
 10) 424.1.1 PROVIDE POOL SQUARE FOOTAGE AND TOTAL
 GALLON CAPACITY.
  
 11) 424.1.1 PROVIDE BATHING LOAD. THE FILTRATION SYSTEM
 FOR SWIMMING POOLS SHALL BE CAPABLE OF PROVIDING A FLOW
 RATE OF AT LEAST 1 GPM FOR EACH LIVING UNIT AT
 TRANSIENT FACILITIES AND 3/4 GPM AT NON TRANSIENT
 FACILITIES. SHOW CALCS.
  
 12) 424.1.6.5.2 THE RECIRCULATION SYSTEM SHALL BE
 DESIGNED TO PROVIDE A MINIMUM OF 4 TURNOVERS OF POOL
 VOLUME PER DAY. PROVIDE CALCS.
  
 13) 107.7.1 POOL PLAN VIEW AND RISER NOT LABELED. SHOW
 WHERE POOL EQUIPMENT WILL BE LOCATED OR TIED INTO POOL
 PIPING. INCLUDE FLOWMETER(S), PRESSURE AND TEMP GAUGES,
 AND FEEDERS.
  
 14) 424.1.6.10.5 A COLLECTOR TANK WITH AN EFFECTIVE
 CAPACITY OF AT LEAST 1 MINUTE OF THE DESIGN FLOW SHALL
 BE PROVIDED. SHOW CALCS.
  
 15) 107.7.1 IS THE RECIRC PUMP SIZED AT THE PROPER
 TDH ACCORDING TO THE TYPE OF FILTER SYSTEM? SHOW
 CALC'S.
  
 16) 424.1.6.5.9.4 POOLS GREATER THAN 30' WIDE HAVE
 FLOOR INLETS ONLY OR A COMBINATION OF FLOOR AND WALL
 INLETS.
  
 17) 424.1.6.5.8 MAIN DRAIN AND SURFACE OVERFLOW SYSTEMS
 WHICH DISCHARGE TO COLLECTOR TANKS SHALL NOT EXCEED 3
 FPS. RETURN LINES SHALL NOT EXCEED 10 FPS. SHOW
 CALC'S.
  
 18) 424.1.6.1.4 A HOSE BIBB WITH A VACUUM BREAKER IS
 REQUIRED IN THE EQUIPMENT ROOM.
  
 19) 107.7.1 PROVIDE MANUFACTURERS SPEC'S FOR
 EQUIPMENT.
  
 MORE COMMENTS MAY FOLLOW.
  
  
 JOE CROASDALE
 PLUMBING PLANS EXAMINER
 TEL. (954) 828-5296
 FAX (954) 828-5275
 JCROASDALE@FORTLAUDERDALE.GOV
2014-03-31 11:06:491)105.3.1 REQUIRE A PERMIT APPLICATION FOR POOL
 PIPING.
  
 2) 107.7.1 PROVIDE DEMO PLAN FOR BATHROOMS.
  
 3) 107.7 E SANITARY PLAN VIEW AND ISO DO NOT MATCH.
  
 4) 706.3 SANITARY FITTINGS SHALL BE INSTALLED IN
 DIRECTION OF FLOW.
  
 5) 107.7 E 3 SIZE WATER PIPING. STATE WHAT MATERIALS
 WILL BE USED.
  
 6) 107.7 C GAS PLAN VIEW DOES NOT MATCH ISO. SHOW METER
 OR SOURCE. SHOW NEW ADDED TO EXISTING. INCLUDE LONGEST
 LENGTH, PIPE SECTION LENGTHS, PIPE SIZING, 2010 FBC
 FUEL GAS TABLE(S) USED, INDIVIDUAL APPLIANCE LOADS, AND
 TOTAL LOAD.
  
 7) 107.7.1 PROVIDE FOR HANDICAP REQUIREMENTS.
  
 8) 107.7 E REQUIRE A SANITARY PLAN VIEW AND ISO FOR
 DRINKING FOUNTAIN ON DECK.
  
 9) 107.7 E PROVIDE WATER HEATER TYPE, LOCATION, SIZE,
 PAN, PAN DRAIN, ETC.
  
 10) 107.7 E SIZE ALL PLANTER, DECK, AND SANITARY
 DRAINS.
  
 11) 107.7.1 PROVIDE COMPLETE POOL PIPING PLAN. SHOW
 WHATS NEW AND/OR EXISTED. SHOW EQUIPMENT, PIPING, ETC.
  
 12) 107.7.1 SHOW POOL SHOWER AND HOSE BIBB LOCATIONS.
  
 13) 107.7.1 SHOW POOL EQUIPMENT DRAIN(S) TO SANITARY.
  
 14) IN GENERAL, PROVIDE A MORE COMPLETE SCOPE. MORE
 COMMENTS MAY FOLLOW.
  
  