Plan Review Details - Permit 15111921

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-15-2016 Cont ID  
Sent By malim Date 07-15-2016 Time 10:29 Rev Time 0.00
Received By malim Date 12-08-2015 Time 06:22 Sent To  
Notes
2016-03-29 06:43:193/29/16
  
 SAME COMMENT
2015-12-08 06:27:03VICTOR BLANCO (954) 828-6565
 VBLANCO@FORTLAUDERDALE.GOV
  
 MUST COMPLY WITH TABLE 1509.7 CLEARANCE BELOW RAISED
 ROOF MOUNTED MECHANICAL UNITS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 12-01-2015 Cont ID  
Sent By connd Date 12-01-2015 Time 13:23 Rev Time 0.00
Received By connd Date 12-01-2015 Time 13:22 Sent To P
Notes
***NONE***

Review Stop F FIRE SAFETY
Rev No 1 Status N Date 12-01-2015 Cont ID  
Sent By strab Date 12-01-2015 Time 08:57 Rev Time 0.00
Received By strab Date 12-01-2015 Time 08:56 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 07-01-2016 Cont ID  
Sent By sadot Date 07-01-2016 Time 09:31 Rev Time 0.50
Received By sadot Date 07-01-2016 Time 09:31 Sent To PLANS RM
Notes
2016-03-12 11:31:41(1) 3/12/16 2ND REVIEW
  
 THE COOLING TOWER(S) REQUIRE AN ANCHOR/ TIE DOWN
 DETAIL, AND AN EQUIPMENT WINDLOAD CERTIFICATION, ON THE
 COOLING TOWER ITSELF. THIS IS 2 SEPERATE ITEMS, THE
 ANCHOR DETAIL AND WINDLOAD CERTIFICATION.
  
 PLEASE CONTACT THE EQUIPMENT MANUFACTURER FOR ANY
 QUESTIONS REGARDING WIND LOAD CERTIFICATIONS. BOTH
 ITEMS ARE REQUIRED PER FBC 2014 MECHANICAL 301.15 CODE
 CRITERIA. THIS CODE REQUIREMENT WENT INTO EFFECT ON
 6/30/15. THE ANCHOR DETAIL IS REQUIRED TO CLEARLY
 INDICATE THE ANCHORING METHOD, NUMBER, QUANTITY,
 DIAMETER, SPACING, ETC, OF THE FASTENER/ ANCHORING
 REQUIREMENTS. THE WIND LOAD CERTIFICATION REQUIREMENT
 IS TO CERTIFY THE COOLING TOWER ITSELF WILL NOT " BLOW
 APART " IN A HIGH WIND EVENT.
  
 (2) ENGINEER DOCUMENTS ARE REQUIRED TO BE SIGNED &
 SEALED ORIGINAL DOCUMENTS, AS THE PRIOR MECHANICAL
 PLANS EXAMINER INDICATED. ENGINEER IS REQUIRED TO BE
 FROM STATE OF FLORIDA.
  
 TONY SADOLF, INTERIM CHIEF MECHANICAL INSPECTOR
 TSADOLF@FORTLAUDERDALE.GOV
 954-828-5983
  
2015-11-30 08:09:14PROVIDE TWO COPIES OF A/C REPLACEMENT DATA SHEET
 (PROVIDED),OR HEAT LOAD CALCULATIONS TO JUSTIFY TONNAGE
 OF NEW COOLING TOWER.
  
 2014 FBCM 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 FLORIDA ADMINISTRATIVE CODE 61G15.23.002
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE'S HANDWRITTEN SIGNATURE ( FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE'S SEAL:
 (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS,
 REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD; AND
 (B) TO ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE.
  
 PAOLO SERAFINI
 MECHANICAL PLANS EXAMINER
 OFFICE 954-828-4993
 PSERAFINI@FORTLAUDERDALE.GOV

Review Stop NOTIFIED NOTIFIED FOR PICKUP
Rev No 1 Status N Date 12-08-2015 Cont ID  
Sent By maldl Date 04-06-2016 Time 07:45 Rev Time 0.00
Received By maldl Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 07-05-2016 Cont ID  
Sent By leibr Date 07-05-2016 Time 11:21 Rev Time 0.00
Received By leibr Date 07-05-2016 Time 11:20 Sent To PLANS RM
Notes
2016-03-30 11:38:401) 107.3.5 E 4 SHOW DRAIN INDIRECTLY WASTED TO
 SANITARY. IF A SANITARY DRAIN CAN NOT BE INSTALLED THE
 CITY WILL ALLOW A VENT STACK TO BE USED. INSTALL AN
 INCREASER AT THE TOP OF THE STACK TO ACT AS A FUNNEL,
 CLAMP WITH EITHER A NO-HUB COUPLING OR FERNCO, VENT
 STACK SHALL BE 3" MINIMUM, NO 2" OR LESS.
  
 2) 105.3.0.1 REQUIRE A PERMIT APPLICATION FROM A
 QUALIFIED PERSON OR FIRM FOR PLUMBING.
  
 JOE CROASDALE PX 954-828-5296
  
2015-12-01 17:57:021) 608.3 SHOW WATER SUPPLY WITH BACKFLOW PROTECTION/AIR
 GAP.
  
 2) 107.3.5 E 4 SHOW DRAIN INDIRECTLY WASTED TO
 SANITARY. INDICATE IF SANITARY DRAIN IS NEW OR
 EXISTING.
  
 3) 105.3.0.1 REQUIRE A PERMIT APPLICATION FROM A
 QUALIFIED PERSON OR FIRM FOR PLUMBING.
  
 JOE CROASDALE PX 954-828-5296

Review Stop Z ZONING
Rev No 1 Status P Date 07-15-2016 Cont ID  
Sent By malim Date 07-15-2016 Time 10:29 Rev Time 0.00
Received By malim Date 12-08-2015 Time 06:21 Sent To  
Notes
2016-03-29 06:42:533/29/16
  
 SAME COMMENT
2015-12-08 06:22:47VICTOR BLANCO (954) 828-6565
 VBLANCO@FORTLAUDERDALE.GOV
  
 47-19.2.Z. ROOF MOUNTED STRUCTURES SUCH AS AIR
 CONDITIONERS AND SATELLITE DISH ANTENNAE SHALL BE
 REQUIRED TO BE SCREENED WITH MATERIAL THAT MATCHES THE
 MATERIAL USED FOR THE PRINCIPAL STRUCTURE AND SHALL BE
 AT LEAST SIX (6) INCHES HIGH ABOVE THE TOP MOST SURFACE
 OF THE ROOF MOUNTED STRUCTURE. VENT PIPES, SKYLIGHTS,
 CUPOLAS, SOLAR COLLECTORS AND CHIMNEYS SHALL NOT BE
 SUBJECT TO THIS PROVISION.