Skip to page body Home Sustainable Development Contact Us

EgovPlus Online Services

Plan Review Details - Permit 15041220

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 04-16-2015 Cont ID  
Sent By harkt Date 04-16-2015 Time 11:46 Rev Time 2.00
Received By harkt Date 04-16-2015 Time 11:45 Sent To PLANS RM
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 04-16-2015 Cont ID  
Sent By drys Date 04-16-2015 Time 11:05 Rev Time 0.50
Received By drys Date 04-16-2015 Time 11:05 Sent To PLANS RM
Notes
***NONE***

Review Stop FLOOD FLOODPLAIN MANAGER
Rev No 1 Status P Date 06-03-2015 Cont ID  
Sent By aquie Date 06-03-2015 Time 13:15 Rev Time 0.00
Received By aquie Date 06-03-2015 Time 13:09 Sent To PLANS RM
Notes
2015-06-03 13:15:52PANEL 386H
  
 SFHA AO1-2-3/X
  
 PRE-FIRM. MULTI-UNIT STRUCTURE.
  
 MECHANICAL EQUIPMENT SHALL BE INSTALLED AT OR ABOVE
 DESIGN FLOOD ELEVATION (BASE FLOOD ELEVATION + 1).

Review Stop L LANDSCAPING
Rev No 1 Status A Date 04-23-2015 Cont ID  
Sent By laurk Date 04-23-2015 Time 12:19 Rev Time 0.50
Received By laurk Date 04-23-2015 Time 12:19 Sent To PLANS RM
Notes
2015-04-23 12:20:29GENERATOR AND FUEL SUPPLY ENCLOSED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 08-22-2015 Cont ID  
Sent By serap Date 08-22-2015 Time 07:09 Rev Time 0.00
Received By serap Date 06-03-2015 Time 13:00 Sent To PLANS RM
Notes
2015-07-01 14:44:51SHOW PIPE SUPPORT FOR EXTENDED SECTION.
 2010 FMC 301.12 WIND RESISTANCE.
 ANCHORING OF ALL OUTDOOR MECHANICAL EQUIPMENT SHALL BE
 DESIGNED TO RESIST PRESSURES IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE CHAPTER 16.
 SHOW DESIGN WIND SPEED, ACCORDING TO BUILDING RISK
 CATAGORY, AND EXPOSURE CATEGORY.
 PROVIDE ENGINEERED DETAIL OR MIAMI-DADE PRODUCT
 APPROVAL REQUIRED.
  
 PAOLO SERAFINI
 MECHANICAL PLANS EXAMINER
 OFFICE 954-828-4993
 PSERAFINI@FORTLAUDERDALE.GOV
2015-06-03 13:06:13FBCM-501.2.1 LOCATION OF EXHAUST OUTLETS.
 THE TERMINATION POINT OF EXHAUST OUTLETS AND DUCTS
 DISCHARGING TO THE OUTDOORS SHALL BE LOCATED WITH THE
 FOLLOWING MINIMUM DISTANCES:
  
 10 FEET FROM THE PROPERTY LINES;
 3 FEET FROM EXTERIOR WALLS AND ROOFS;
 10 FEET FROM OPERABLE OPENINGS INTO BUILDINGS.
  
 PAOLO SERAFINI
 MECHANICAL PLANS EXAMINER
 OFFICE 954-828-4993
 PSERAFINI@FORTLAUDERDALE.GOV

Review Stop NOTIFIED NOTIFIED FOR PICKUP
Rev No 1 Status N Date 06-03-2015 Cont ID  
Sent By mcinr Date 08-24-2015 Time 14:18 Rev Time  
Received By quina Date 06-03-2015 Time 14:18 Sent To  
Notes
2015-08-25 10:57:34PREPAID ON FLAIR AT RECEPTION DESK FOR PICK UP-DPS
2015-08-24 11:08:45EMAILED...BOX.
2015-07-24 15:41:12EMAILED...BOX.

Review Stop P PLUMBING
Rev No 1 Status P Date 08-20-2015 Cont ID  
Sent By demaj Date 08-20-2015 Time 08:36 Rev Time 0.00
Received By demaj Date 08-20-2015 Time 15:05 Sent To PLANS RM
Notes
2015-08-20 15:07:25PLAN REVIEW BY JOE KAJAK.
2015-07-24 14:34:491) 409.2 SHOW PIPING WITH SHUT OFF VALVE AFTER METER
 AND NOTE IF ANYTHING ELSE IS CONNECTED TO THE GAS
 METER.
  
 2) 402.4(2) MINIMUN THREE INCH PIPING REQUIRED TO THE
 NEW GENERATOR.
  
 3) 105.1 BROWARD COUNTY APPROVAL REQUIRED ON NEW
 GENERATOR.
  
 JOE DEMAIO
 CHIEF PLUMBING INSPECTOR
 OFFICE 954-828-5246
 FAX 954-828-5275
 JDEMAIO@FORTLAUDERDALE.GOV
2015-04-20 08:36:171- SHOW GAS PIPING WITH CALCUALTIONS AS PER FUEL GAS
 CODE 2010.
  
 2- PERMIT APP REQUIRED FOR GAS, CAN SUBMIT TBD.
  
 GREG DIAZ
 PLUMBING REVIEW.
 954 828-3544

Review Stop Z ZONING
Rev No 1 Status P Date 07-21-2015 Cont ID  
Sent By blanv Date 07-21-2015 Time 14:17 Rev Time 0.00
Received By blanv Date 04-22-2015 Time 08:56 Sent To  
Notes
2015-04-22 08:56:48CLARIFY, IS THIS NEW GENERATOR IS AFFECTING ANY
 PARKING??
 IF NO--IT IS OK TO APPROVE
 IF YES--JUSTIFY PARKING